Refrigerant charge distribution in brine-to-water heat pump using R290 as refrigerant

Other Title
Distribution de la charge en frigorigène dans une pompe à chaleur saumure/eau utilisant le R290 comme frigorigène
Abstract
This paper presents experimental results from a brine-to-water heat pump used for space heating at low temperature, with a low refrigerant charge of R290 (propane). Performance and refrigerant distribution were analysed in every test condition studied. Performance results show a declared heating capacity of , obtaining a specific capacity (Cc) of 48.7 kW rmkg-1 and a seasonal coefficient of performance of 4.01. In terms of refrigerant distribution, at the nominal point, 41.5% of the refrigerant is located in the compressor, mainly dissolved in the oil, and the rest is separated almost evenly in both heat exchangers, 23.9% in the condenser and 27.8% in the evaporator; having the lines and accessories (pneumatic-ball valves) the remaining 6.8%. Due to this fact, reducing oil solubility by heating the crankcase or increasing the superheat (SH) has a positive impact on the refrigerant charge reduction, but it also affects the coefficient of performance.
Author(s)
Sánchez-Moreno-Giner, Luis
Fraunhofer-Institut für Solare Energiesysteme ISE  
Methler, Timo
Fraunhofer-Institut für Solare Energiesysteme ISE  
Barceló-Ruescas, Francisco
Polytechnic University of Valencia (UPV)
Gonzalvez-Maciá, José
Polytechnic University of Valencia (UPV)
Journal
International journal of refrigeration  
Open Access
File(s)
Download (1.83 MB)
Rights
CC BY-NC-ND 4.0: Creative Commons Attribution-NonCommercial-NoDerivatives
DOI
10.1016/j.ijrefrig.2022.10.013
10.24406/publica-1723
Language
English
Fraunhofer-Institut für Solare Energiesysteme ISE  
Keyword(s)
  • brine-to-water heat pump

  • low refrigerant charge

  • R290